CONDUCTIVITY CONTROLLER CC-421


CC-421 is a stationary device used for continuous conductivity and temperature measurements in clear water or sewage. The device is available in three versions
- equipped with two relays;
- equipped with 0 ÷ 20 mA or 4 ÷ 20 mA, current loop;
- equipped with RS-232 output to connect with a computer.
Optionally, the connection may be made by USB output with use of RS to USB converter (additional equipment).
The device enables 1-point calibration of the measuring cell by entering the constant K value or in standard solution with value set in the device's memory.
It is possible to calibrate it without the need of disconnecting the outputs.

Characteristic features:


The controller may cooperate with GXZ-1t immersible head or with GXP-1t flow head and GXP-01 head for measurements in outflow. The cells are selected depending on the measurement conditions.



TECHNICAL DATA
Function Conductivity Salinity Temperature
Range 0 ÷ 199.9 mS/cm,
4 subranges - autorange
NaCl 0 ÷ 150 g/l -50.0 ÷ 199.9 °C
Accuracy (± 1 digit) ±0.25 %* ±2 %* ±0.1 **
Temp. compensation -5 ÷ 70 °C -5 ÷ 70 °C -
α coefficient constant 2 %/°C constant 2 %/°C -
K constant 0.010 ÷ 1,999 cm-1 - -
Temperature sensor Pt-1000
Relays' parameters 2A/250VAC/30VDC
Isolation class according to PN-83/T-06500
Radioelectric interference N level
Power supply 12 V / 100 mA power adapter
Dimensions (mm) L = 149; W = 82; H=22
Weight 220 g
* The accuracy of the meter only.
** The accuracy of the meter only. The total error includes the meters and probe's accuracy. In the range 0 ÷ 100 °C the acceptable error of the probe with Pt-1000B resistor: ±0.8 °C , with Pt-1000A resistor: ±0.35 °C.